K-FLEX ST Elastomeric Pipe Insulation Tube - 2m Length
Our dispatch dates are real – worked out from our suppliers’ current lead times, never rounded down to win the sale.
Similar In stock now, ready to dispatch
Armaflex EVO Pipe Insulation Lagging — Class O Black Nitrile Foam 2m – 6mm / 6mm / 2m LengthRated −50°C to +110°C (this product −165°C to +110°C)
Key specifications
- Fire rating
- Euroclass BL-s2,d0 (EN 13501-1)
- Service temperature
- -165°C to +110°C (below -40°C consult K-Flex technical department)
- Thermal conductivity
- λ ≤ 0.033 W/(m·K) at 0°C, 0.037 at +40°C (up to 25 mm); ≤ 0.036 at 0°C, 0.040 at +40°C (over 25 mm)
- Standard
- EN 14304
Source: manufacturer's technical datasheet · View datasheet
How to measure?
Pipe insulation sizes refer to the outside diameter of the pipe — not the bore (internal diameter).
|←— OD —→|Wrap a tape measure around the pipe, divide by π (3.14) to get the OD. Or use calipers across the outside of the pipe directly.
K-FLEX ST Elastomeric Pipe Insulation Tube
K-FLEX ST is a flexible closed-cell elastomeric foam insulation tube for refrigeration, air-conditioning, chilled-water, heating and plumbing pipework. The closed-cell structure provides thermal insulation and high resistance to water-vapour diffusion, helping to control condensation when joints and seams are correctly sealed.
Product Details
- Brand: K-FLEX
- Range: ST
- Material: Flexible closed-cell elastomeric foam
- Colour: Black
- Tube length: 2 metres
- Standard: EN 14304
- Operating temperature for K-FLEX ST tube: -165°C to +110°C
- For applications below -40°C, confirm suitability with K-FLEX technical support
- Thermal conductivity at 0°C: ≤ 0.033 W/(m·K) for thicknesses up to 25mm; ≤ 0.036 W/(m·K) for thicknesses over 25mm
- Water-vapour diffusion resistance factor (μ): ≥ 10,000 up to 25mm thickness; ≥ 7,000 over 25mm
- Euroclass: BL-s2,d0
- Suitable for refrigeration, air-conditioning, chilled-water, heating and plumbing services
Installation
Choose the tube size to suit the outside diameter of the pipe and the required insulation thickness. Seal longitudinal joints, butt joints and fittings in accordance with K-FLEX installation guidance using a compatible K-FLEX adhesive where required, maintaining continuity of the vapour-control layer on condensation-risk services.